Brand Name :Fullde
Model Number :500KW-400V
Certification :CE, ISO9001
Place of Origin :Dongguan,China
MOQ :one set
Price :Negotiable
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :100 Set/Sets per Month
Delivery Time :25 working days
Packaging Details :Packaged by Wooden Case with Soft Protective Material
Winding :100% Copper Wire
Governor Type :Electronic
Pack :Wooden packaging,Carton packaging
Color :white/blue
Frequency :50HZ/60HZ
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Resistive Load Bank for Generator Testing 500KW-400V Generator Load Bank

Application of generator Load Bank:

1. Large generator system testing in ocean engineering, drilling facilities,ship construction etc;


2. Factory testing for generator, static voltage characteristic test, speed characteristic test;


3. Marine generator overload protection test,parallel operation test,reverse power and current protection test;


4. Assist shipyard in mooring test,sea trial test;


5. Assist with the acceptance of the vessel generator test;


6. Eliminate the carbon deposition of generator;


7. As the generator loading system;


8. Periodic running test for standby generator;


9. UPS inspection and maintenance;


10. Ship battery charging/discharging system testing;


11. The acceptance of new system and testing of servicing equipment.

Main functions:


1. Can adjust various load power within rated power;

2. Harmonic wave analysis: dispaly 3 phase voltage, current, active power, wattles power, apparent power, power factor, frequency and running time etc,in stable state,sine wave and phase sequence may be displayed,display relevant voltage when testing transient parameter,frequency transient curve and can analyze 2-50 harmonic waves,display or output harmonic wave componet and distortion factor analysis report;

3. Testing reports may be inquired, displayed and printed based on time, model, machine number,the minimum resolution time of stable state record is 1s, transient;
Control mode: manual control (control panel) with remote controller box or PC control.
Display meters: multi-function digital meter or generator tester.
Protection: Over load protection, over heat protection, short circuit protection, Emergency stops switch, etc;


4. Over-heat protection: There will be sound-light alarm when temperature is over safety thresholds.

Technical Parameters for reference:

System components Load bank, resistive load,data collection, automatic control and manual control, electrical control, cooling devices and auxiliary control,Industrial machines, printer.
Total discharge power 500KW
Resistive load stalls step: 5KW
Test voltage Three-phase AC400V
Test Frequency 50Hz
Resistance tube Insulation resistance of each resistor above DC500V 100MΩ , Pressure AC2000V 1 minute, Resistance to high temperature.
Load connection Star (three-phase four -wire)
Loading precision ±3%
Work way Continuous work
Working power 480VAC/50Hz/Three-phase four-wire system; (reservation terminals)
Operator terminal IPC / software, full realization of automated control
Control mode Manual control / computer software auto control
Measured Control Function Load subtraction control, extended load automatic identification synchronization control
IPC detection function I, V, HZ, KW, COSΦ etc.Real-time display, electrical performance testing, curves and report output, system electrical parameters monitoring, automatic data acquisition;
Parameter record Form through EXCEL, curves pictures saved by WORD document
Parameter display three-phase voltage, three- phase current, apparent power, active power, reactive power, power factor, frequency, etc.;
Load protection Overvoltage, overcurrent, high temperature, air flow and fan failure protection;
Fault alarm Fan failure, load high temperature alarm
Dimension 1300*1600*1700
Weight 600kg
Applicable Scope For marine diesel generator sets, land diesel generators, power inverters, UPS systems