White Colour Portable Type 800KW 400V Resistor Generator Load Bank
Applications:
With advanced reasonable structure, high efficiency, low vibration and noise, smooth running, high reliability, easy handling, Fullde generators are widely used in national defense, telecommunications, construction site, commercial buildings, industrial and mining sites, oil fields, roads, ports, villas, banks, hospitals etc.
Features:
1. Control Mode: With total load control function,can complete the sudden increase or decrease of load of any percentage(intelligently controlled,manual/automatic can be selected).
2. DC type or AC type;Fixed type or Variable type available.
3. Display for voltage and Current,temperature and power of meters.
4. The unit is movable on castors.(portable)
5. Customer special requirement available.
6. Suitable for educational modeling applications,load testing,industrial machinery,electric power distribution,instruments and automation control installations.
7. With software programmable control, graphs of current, voltage, frequency, power factor, power can be displayed, saved and printed.
Control mode: manual control (control panel) with remote controller box or PC control.
Our duty:
• All load banks have to pass the strict inspection and tested before shipping.
• After receive the goods, We accept yur feedback at first time.
• We could provide installation guide, if you have need, we could give you
global service.
• Provide customized solution.
• Our Sales are 24-hours online for our request.
Technical Parameters for reference:
System components | Load bank, resistive load,data collection, automatic control and manual control, electrical control, cooling devices and auxiliary control,Industrial machines, printer. |
Total discharge power | 800KW |
Resistive load stalls | step: 5KW |
Test voltage | Three-phase AC400V |
Test Frequency | 50Hz |
Resistance tube | Insulation resistance of each resistor above DC500V 100MΩ , Pressure AC2000V 1 minute, Resistance to high temperature. |
Load connection | Star (three-phase four -wire) |
Loading precision | ±3%; |
Work way | Continuous work |
Working power | 480VAC/50Hz/Three-phase four-wire system; (reservation terminals) |
Operator terminal | IPC / software, full realization of automated control |
Control mode | Manual control / computer software auto control |
Measured Control Function | Load subtraction control, extended load automatic identification synchronization control |
IPC detection function | I, V, HZ, KW, COSΦ etc.Real-time display, electrical performance testing, curves and report output, system electrical parameters monitoring, automatic data acquisition; |
Parameter record | Form through EXCEL, curves pictures saved by WORD document |
Parameter display | three-phase voltage, three- phase current, apparent power, active power, reactive power, power factor, frequency, etc.; |
Load protection | Overvoltage, overcurrent, high temperature, air flow and fan failure protection; |
Fault alarm | Fan failure, load high temperature alarm |
Dimension | 2500*1600*1800 |
Weight | 1500kg |
Applicable Scope | For marine diesel generator sets, land diesel generators, power inverters, UPS systems |